Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.
A computer-room air handler: a deep chilled-water coil and a draw-through plug fan, no outside air, no heater — a data hall is cooled all year. In the example data centre it breathes two halls' return air and takes 14 °C water from the chiller block; the design point here is at 14 °C too. Published as an example; the figures below are solved from this model, not copied from a datasheet.
Example60–120 kW coolingEUExample system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.
Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.
| Component | Kind | Duty |
|---|---|---|
| Chilled-water coil | waterCoil | 105.4 kW |
| Plug fan (draw-through) | fan | -4.8 kW |
Publish your own range and this slot becomes your branded page — your data, your logo, your product link, and quote requests that reach you. Free to register and free to publish.