Catalog · Baltimore Aircoil

Baltimore Aircoil FXT-0712C-K cooling tower

Cooling tower — Cooling tower — 946 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 26.6 m³/s of air.

A Baltimore Aircoil listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Rated water35.0 to 29.4 °C
Rated entering wet bulb25.6 °C
Water flow at the rating40.69 kg/s
Air flow at the rating26.62 m³/s
Heat rejected at the rating946 kW
Fan motor (nameplate)7.46 kW
Typeopen — the loop water over the fill
Cabinet3683 mm x 3353 mm

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.