Catalog · Baltimore Aircoil

Baltimore Aircoil FXV-1212C-20D-P closed-circuit cooler

Cooling tower — Closed-circuit cooler — 990 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 52.7 m³/s of air.

A Baltimore Aircoil listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Rated water35.0 to 29.4 °C
Rated entering wet bulb25.6 °C
Water flow at the rating42.58 kg/s
Air flow at the rating52.70 m³/s
Heat rejected at the rating990 kW
Fan motor (nameplate)29.83 kW
Typeclosed circuit — the loop fluid in a coil under the spray
Cabinet5055 mm x 5055 mm

Open this part in the app — as a component of its own, carrying the catalog's figures; or open the builder and pick it from the catalog picker. The solver runs it with the catalog's own data, at your design point or across a year of weather.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.