Cooling tower — Closed-circuit cooler — 1336 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 78.7 m³/s of air.
A Baltimore Aircoil listing, from the manufacturer's published data.
Units: SI · US customary
| Rated water | 35.0 to 29.4 °C |
| Rated entering wet bulb | 25.6 °C |
| Water flow at the rating | 57.46 kg/s |
| Air flow at the rating | 78.66 m³/s |
| Heat rejected at the rating | 1336 kW |
| Fan motor (nameplate) | 29.83 kW |
| Type | closed circuit — the loop fluid in a coil under the spray |
| Cabinet | 5817 mm x 5817 mm |
Open this part in the app — as a component of its own, carrying the catalog's figures; or open the builder and pick it from the catalog picker. The solver runs it with the catalog's own data, at your design point or across a year of weather.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.