Catalog · Baltimore Aircoil

Baltimore Aircoil PFI-2418N-3D4DS-P2 closed-circuit cooler

Cooling tower — Closed-circuit cooler — 2239 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 125.6 m³/s of air.

A Baltimore Aircoil listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Rated water35.0 to 29.4 °C
Rated entering wet bulb25.6 °C
Water flow at the rating96.27 kg/s
Air flow at the rating125.63 m³/s
Heat rejected at the rating2239 kW
Fan motor (nameplate)59.66 kW
Typeclosed circuit — the loop fluid in a coil under the spray
Cabinet5842 mm x 5842 mm

Open this part in the app — as a component of its own, carrying the catalog's figures; or open the builder and pick it from the catalog picker. The solver runs it with the catalog's own data, at your design point or across a year of weather.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.