Catalog · Baltimore Aircoil

Baltimore Aircoil Series V closed circuit VF1-144N-31R closed-circuit cooler

Cooling tower — Closed-circuit cooler — 648 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 36.0 m³/s of air.

A Baltimore Aircoil listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Rated water35.0 to 29.4 °C
Rated entering wet bulb25.6 °C
Water flow at the rating27.88 kg/s
Air flow at the rating36.01 m³/s
Heat rejected at the rating648 kW
Fan motor (nameplate)44.74 kW
Typeclosed circuit — the loop fluid in a coil under the spray
Cabinet4140 mm x 4140 mm

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

towersBaltimore Aircoil Series 1500 S15E-1212-07JN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07JN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07KN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07KN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07LC cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07LC-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09JN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09JN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09KN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09KN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09LC cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09LC-2 cooling tower

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.