Catalog · Baltimore Aircoil

Baltimore Aircoil Series V VT1-N370-Q cooling tower

Cooling tower — Cooling tower — 1621 kW rejected, water 35.0 to 29.4 °C at a 25.6 °C wet bulb, 37.8 m³/s of air.

A Baltimore Aircoil listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

Rated water35.0 to 29.4 °C
Rated entering wet bulb25.6 °C
Water flow at the rating69.71 kg/s
Air flow at the rating37.83 m³/s
Heat rejected at the rating1621 kW
Fan motor (nameplate)37.28 kW
Typeopen — the loop water over the fill
Cabinet4445 mm x 4445 mm

Open this part in the app — as a component of its own, carrying the catalog's figures; or open the builder and pick it from the catalog picker. The solver runs it with the catalog's own data, at your design point or across a year of weather.

Same family

towersBaltimore Aircoil Series 1500 S15E-1212-07JN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07JN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07KN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07KN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07LC cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-07LC-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09JN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09JN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09KN cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09KN-2 cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09LC cooling tower
towersBaltimore Aircoil Series 1500 S15E-1212-09LC-2 cooling tower

How the model reads against this maker's data

Cooling-tower model against a third maker's whole open-tower range, one fill exponent per range19 281 over 438 machinesRMS 0.11 K (FXT, Series 1500), 0.13 K (PT2), 0.15 K (Series 3000), 0.20 K (Series V); every mean within ±0.09 K, worst 0.95 K. One constant per range was chosen on these tables: how the fill's transfer moves with water loading (−0.9 to −1.3, against −0.7 on EVAPCO's table), chosen on half of each range's models and confirmed on the other; the counterflow ranges are read through Merkel's balance integrated and the two crossflow ranges marched as crossflow. On the old single-chord model and one shared exponent the same tables read 0.31–0.48 K, with a trend of +0.5 K at a 50 °F wet bulb to −0.5 K at 90 °F on every range; what is left of it is up to 0.17 K cold at 85–90 °F
Closed-circuit cooler (an evaporative wet coil whose spray film varies along the coil), two coil constants per range18 831 over 392 machinesRMS 0.10 K (FXV), 0.09 K (PFi), 0.10 K (Series V closed circuit). Two constants per coil design were chosen on these tables — the split between the fluid-side and air-side conductances (2, 1, 4) and how the fluid side moves with the fluid's flow (−0.8, −0.8, −0.6) — each the same on either half of the range's models. The second has an independent reading: the fluid side is the tube film in series with the spray film outside the tube, and a tube-side calculation from each coil's printed volume and pressure drop, using nothing from these tables, puts it at −0.5 to −0.8 whatever the unpublished tube bore. On the earlier constants (3 and −0.2, the tube film alone) the same tables read 0.17–0.32 K, and 0.2–0.5 K cold at the high wet bulbs. On the points a uniform film also reaches, the gradient reads 0.09–0.10 K against the uniform film's 0.15–0.19 K at the same constants; under the earlier constants the two read within 0.01 K

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.