Catalog · Copeland

Copeland 2DB3F25KE-TFD (R513A Discus recip, 60 Hz, MD)

Compressor — R513A compressor — 18.2 kW cooling, 6.23 kW input, COP 2.92 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 2DB3F25KE-TFD (R513A Discus recip, 60 Hz, MD)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C18.19 kW
Input power @ 7.2/54.4 °C6.23 kW
COP @ 7.2/54.4 °C2.92

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1010.582.414.39
-20 / 308.173.202.55
-10 / 1016.262.376.85
-10 / 3013.203.793.48
-10 / 607.904.841.63
0 / 3020.024.084.91
0 / 6012.005.842.06

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 2DB3F25KE-TFC (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 2DB3F25KE-TFD (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 2DB3F25KE-TFC (R407F Discus recip, 60 Hz, LD)R407F
compressorsCopeland 2DB3F25KE-TFC (R448A Discus recip, 60 Hz, LD)R448A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy