Compressor — R513A compressor — 29.5 kW cooling, 10.33 kW input, COP 2.86 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 3DF3F40KL-TFD (R513A Discus recip, 60 Hz, MD) |
| Refrigerant | R513A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 29.55 kW |
| Input power @ 7.2/54.4 °C | 10.33 kW |
| COP @ 7.2/54.4 °C | 2.86 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 17.04 | 3.90 | 4.37 |
| -20 / 30 | 13.31 | 5.26 | 2.53 |
| -10 / 10 | 26.28 | 3.89 | 6.75 |
| -10 / 30 | 21.41 | 6.25 | 3.43 |
| -10 / 60 | 12.91 | 8.01 | 1.61 |
| 0 / 30 | 32.25 | 6.70 | 4.81 |
| 0 / 60 | 19.77 | 9.75 | 2.03 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 3DF3F40KL-TFD (R407A Discus recip, 60 Hz, LD) | R407A |
| compressors | Copeland 3DF3F40KL-TFD (R407C Discus recip, 50 Hz, LD) | R407C |
| compressors | Copeland 3DF3F40KL-TFD (R407C Discus recip, 60 Hz, LD) | R407C |
| compressors | Copeland 3DF3F40KL-TFD (R407F Discus recip, 60 Hz, LD) | R407F |
| compressors | Copeland 3DF3F40KL-TFD (R448A Discus recip, 60 Hz, LD) | R448A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.