Compressor — R407C compressor — 44.5 kW cooling, 21.84 kW input, COP 2.04 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 3DS3F46KL-TFD (R407C Discus recip, 60 Hz, LD) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 44.53 kW |
| Input power @ 7.2/54.4 °C | 21.84 kW |
| COP @ 7.2/54.4 °C | 2.04 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 11.03 | 5.05 | 2.19 |
| -40 / 30 | 6.34 | 4.70 | 1.35 |
| -30 / 10 | 18.68 | 6.35 | 2.94 |
| -30 / 30 | 12.80 | 6.78 | 1.89 |
| -30 / 60 | 5.17 | 6.91 | 0.75 |
| -20 / 10 | 28.22 | 6.27 | 4.50 |
| -20 / 30 | 21.34 | 8.51 | 2.51 |
| -20 / 60 | 12.23 | 10.04 | 1.22 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland 3DS3F46KL-TFD (R407A Discus recip, 60 Hz, LD) | R407A |
| compressors | Copeland 3DS3F46KL-TFD (R407F Discus recip, 60 Hz, LD) | R407F |
| compressors | Copeland 3DS3F46KL-TFD (R448A Discus recip, 60 Hz, LD) | R448A |
| compressors | Copeland 3DS3F46KL-TFD (R507 Discus recip, 50 Hz, LD) | R507 |
| compressors | Copeland 3DS3F46KL-TFD (R513A Discus recip, 60 Hz, MD) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.