Copeland 3DS3F46KL-TFD (R507 Discus recip, 50 Hz, LD)

Compressor — R507 compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3DS3F46KL-TFD (R507 Discus recip, 50 Hz, LD)
RefrigerantR507
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1010.304.412.34
-40 / 308.615.371.60
-40 / 505.805.521.05
-30 / 1017.885.523.24
-30 / 3014.397.002.05
-30 / 5010.547.991.32
-20 / 1028.986.704.33
-20 / 3022.588.582.63
-20 / 5016.5810.271.61

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 3DS3F46KL-TFD (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 3DS3F46KL-TFD (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 3DS3F46KL-TFD (R407F Discus recip, 60 Hz, LD)R407F
compressorsCopeland 3DS3F46KL-TFD (R448A Discus recip, 60 Hz, LD)R448A
compressorsCopeland 3DS3F46KL-TFD (R513A Discus recip, 60 Hz, MD)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy