Catalog · Copeland

Copeland 3PA3R12ML-TFD (R410A Discus recip, 60 Hz, MD)

Compressor — R410A compressor — 53.5 kW cooling, 18.77 kW input, COP 2.85 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 3PA3R12ML-TFD (R410A Discus recip, 60 Hz, MD)
RefrigerantR410A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C53.47 kW
Input power @ 7.2/54.4 °C18.77 kW
COP @ 7.2/54.4 °C2.85

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1034.137.244.72
-20 / 3027.2210.042.71
-20 / 6014.0911.641.21
-10 / 1051.407.007.35
-10 / 3042.1811.243.75
-10 / 6023.7715.571.53
0 / 3062.1911.435.44
0 / 6036.0818.781.92

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy