Compressor — R410A compressor — 36.0 kW cooling, 12.83 kW input, COP 2.81 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 3PADF35KE-TFD (R410A Discus recip, 60 Hz, LD) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 47.2 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 36.05 kW |
| Input power @ 7.2/54.4 °C | 12.83 kW |
| COP @ 7.2/54.4 °C | 2.81 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 10 | 10.78 | 4.58 | 2.35 |
| -40 / 30 | 8.04 | 5.69 | 1.41 |
| -40 / 50 | 4.69 | 6.52 | 0.72 |
| -30 / 10 | 18.30 | 5.58 | 3.28 |
| -30 / 30 | 14.01 | 6.96 | 2.01 |
| -30 / 50 | 8.97 | 7.99 | 1.12 |
| -20 / 10 | 29.21 | 6.20 | 4.71 |
| -20 / 30 | 23.05 | 8.57 | 2.69 |
| -20 / 50 | 16.00 | 10.51 | 1.52 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.