Compressor — R410A compressor — 58.1 kW cooling, 20.55 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland 3PADR13ME-TFD (R410A Discus recip, 60 Hz, MD) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 26.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 58.06 kW |
| Input power @ 7.2/54.4 °C | 20.55 kW |
| COP @ 7.2/54.4 °C | 2.83 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 36.93 | 7.75 | 4.77 |
| -20 / 30 | 29.46 | 10.90 | 2.70 |
| -20 / 60 | 16.92 | 13.78 | 1.23 |
| -10 / 10 | 56.05 | 7.52 | 7.45 |
| -10 / 30 | 45.27 | 12.11 | 3.74 |
| -10 / 60 | 26.81 | 17.51 | 1.53 |
| 0 / 30 | 66.69 | 12.42 | 5.37 |
| 0 / 60 | 40.01 | 20.65 | 1.94 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.