Catalog · Copeland

Copeland 4DHXR16ME-AWX (R134A Discus recip, 60 Hz, AC)

Compressor — R134a compressor — 46.8 kW cooling, 15.77 kW input, COP 2.97 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 4DHXR16ME-AWX (R134A Discus recip, 60 Hz, AC)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C46.78 kW
Input power @ 7.2/54.4 °C15.77 kW
COP @ 7.2/54.4 °C2.97

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 4029.4010.412.82
0 / 4046.1711.953.86
0 / 7028.3615.861.79
10 / 4069.2312.705.45
10 / 7044.9219.342.32
20 / 4099.9912.308.13
20 / 7067.5622.163.05

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 4DHXR16ME-TSK (R513A Discus recip, 60 Hz, MD)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy