Catalog · Copeland

Copeland 6DVNF13ML-AWD (R404A Discus recip, 60 Hz, LD)

Compressor — R404A compressor — 166.1 kW cooling, 56.29 kW input, COP 2.95 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DVNF13ML-AWD (R404A Discus recip, 60 Hz, LD)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C166.14 kW
Input power @ 7.2/54.4 °C56.29 kW
COP @ 7.2/54.4 °C2.95

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 1032.3217.541.84
-40 / 3029.4919.301.53
-40 / 5018.0219.040.95
-30 / 1064.6320.743.12
-30 / 3052.2725.412.06
-30 / 5034.0628.451.20
-20 / 10100.7924.514.11
-20 / 3079.1831.532.51
-20 / 5054.5237.341.46

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DVNF13ML-AWD (R404A Discus recip, 50 Hz, LD)R404A
compressorsCopeland 6DVNF13ML-AWD (R407A Discus recip, 50 Hz, LD)R407A
compressorsCopeland 6DVNF13ML-AWD (R407A Discus recip, 60 Hz, LD)R407A
compressorsCopeland 6DVNF13ML-AWD (R407C Discus recip, 50 Hz, LD)R407C
compressorsCopeland 6DVNF13ML-AWD (R407C Discus recip, 60 Hz, LD)R407C
compressorsCopeland 6DVNF13ML-AWD (R448A Discus recip, 60 Hz, LD)R448A
compressorsCopeland 6DVNF13ML-AWD (R507 Discus recip, 50 Hz, LD)R507
compressorsCopeland 6DVNF13ML-AWD (R507 Discus recip, 60 Hz, LD)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy