Copeland 6DVNR36ME-AWX (R134A Discus recip, 60 Hz, MD)

Compressor — R134a compressor — 98.7 kW cooling, 33.19 kW input, COP 2.97 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland 6DVNR36ME-AWX (R134A Discus recip, 60 Hz, MD)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C98.65 kW
Input power @ 7.2/54.4 °C33.19 kW
COP @ 7.2/54.4 °C2.97

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1066.2414.504.57
-20 / 3043.7316.202.70
-10 / 1093.1216.055.80
-10 / 3068.6619.583.51
-10 / 6041.3124.931.66
0 / 30109.5321.505.09
0 / 6066.9130.842.17

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland 6DVNR36ME-AWX (R507 Discus recip, 50 Hz, LD)R507
compressorsCopeland 6DVNR36ME-AWX (R507 Discus recip, 60 Hz, LD)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy