Catalog · Copeland

Copeland AFF10C1E-IAZ (R134A hermetic recip, 50 Hz, EF)

Compressor — R134a compressor — 0.9 kW cooling, 0.43 kW input, COP 2.16 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland AFF10C1E-IAZ (R134A hermetic recip, 50 Hz, EF)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool36.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C0.92 kW
Input power @ 7.2/54.4 °C0.43 kW
COP @ 7.2/54.4 °C2.16

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 36.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 300.250.171.48
-30 / 400.210.181.18
-20 / 300.420.202.04
-20 / 400.360.231.61
-20 / 600.250.251.00
-10 / 300.670.242.80
-10 / 400.590.282.13
-10 / 600.420.331.29

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland AFF10C1E-IA3 (R134A hermetic recip, 60 Hz, EF)R134a
compressorsCopeland AFF10C1E-IAA (R450A hermetic recip, 60 Hz, EF)R450A
compressorsCopeland AFF10C1E-IAZ (R513A hermetic recip, 50 Hz, EF)R513A
compressorsCopeland AFF10C1E-IA3 (R513A hermetic recip, 60 Hz, EF)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy