Catalog · Copeland

Copeland AFF13C1E-IA3 (R513A hermetic recip, 60 Hz, EF)

Compressor — R513A compressor — 1.2 kW cooling, 0.83 kW input, COP 1.48 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland AFF13C1E-IA3 (R513A hermetic recip, 60 Hz, EF)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool36.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.22 kW
Input power @ 7.2/54.4 °C0.83 kW
COP @ 7.2/54.4 °C1.48

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 36.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 300.380.291.29
-30 / 400.330.301.09
-20 / 300.600.381.58
-20 / 400.530.391.36
-20 / 600.380.420.89
-10 / 300.920.501.82
-10 / 400.810.521.58
-10 / 600.590.551.07

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland AFF13C1E-IAZ (R134A hermetic recip, 50 Hz, EF)R134a
compressorsCopeland AFF13C1E-IA3 (R450A hermetic recip, 60 Hz, EF)R450A
compressorsCopeland AFF13C1E-IAZ (R513A hermetic recip, 50 Hz, EF)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy