Compressor — R290 compressor — 1.9 kW cooling, 0.86 kW input, COP 2.18 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ASE39C5U-CAA (R290 hermetic recip, 60 Hz, MT) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.5 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 1.89 kW |
| Input power @ 7.2/54.4 °C | 0.86 kW |
| COP @ 7.2/54.4 °C | 2.18 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 0.99 | 0.47 | 2.11 |
| -20 / 40 | 0.85 | 0.51 | 1.68 |
| -10 / 30 | 1.49 | 0.55 | 2.71 |
| -10 / 40 | 1.31 | 0.61 | 2.16 |
| -10 / 60 | 0.90 | 0.72 | 1.25 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.