Compressor — R290 compressor — 2.3 kW cooling, 1.29 kW input, COP 1.79 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ASE59C6U-CFA (R290 hermetic recip, 60 Hz, EM) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 38.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 2.30 kW |
| Input power @ 7.2/54.4 °C | 1.29 kW |
| COP @ 7.2/54.4 °C | 1.79 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 0.53 | 0.41 | 1.30 |
| -40 / 40 | 0.44 | 0.42 | 1.06 |
| -30 / 30 | 0.86 | 0.53 | 1.62 |
| -30 / 40 | 0.74 | 0.55 | 1.34 |
| -30 / 60 | 0.52 | 0.59 | 0.87 |
| -20 / 30 | 1.36 | 0.65 | 2.07 |
| -20 / 40 | 1.19 | 0.69 | 1.71 |
| -20 / 60 | 0.84 | 0.77 | 1.08 |
| 0 / 30 | 2.85 | 0.90 | 3.16 |
| 0 / 40 | 2.49 | 1.00 | 2.50 |
| 0 / 60 | 1.76 | 1.20 | 1.46 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.