Compressor — R290 compressor — 0.7 kW cooling, 0.34 kW input, COP 2.04 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ASM24C7U-IAI (R290 hermetic recip, 50 Hz, EM) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 38.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 0.70 kW |
| Input power @ 7.2/54.4 °C | 0.34 kW |
| COP @ 7.2/54.4 °C | 2.04 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 0.08 | 0.09 | 0.92 |
| -40 / 40 | 0.12 | 0.12 | 0.98 |
| -30 / 30 | 0.21 | 0.14 | 1.48 |
| -30 / 40 | 0.23 | 0.17 | 1.31 |
| -30 / 60 | 0.15 | 0.19 | 0.80 |
| -20 / 30 | 0.37 | 0.18 | 2.00 |
| -20 / 40 | 0.36 | 0.21 | 1.68 |
| -20 / 60 | 0.26 | 0.26 | 1.01 |
| 0 / 30 | 0.82 | 0.24 | 3.46 |
| 0 / 40 | 0.73 | 0.26 | 2.79 |
| 0 / 60 | 0.55 | 0.36 | 1.53 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ASM24C7U-IAA (R290 hermetic recip, 60 Hz, EM) | R290 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.