Compressor — R22 compressor — 5.4 kW cooling, 1.97 kW input, COP 2.74 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CR24K6M-TFD (R22 hermetic recip, 50 Hz, HT) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 5.40 kW |
| Input power @ 7.2/54.4 °C | 1.97 kW |
| COP @ 7.2/54.4 °C | 2.74 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 40 | 1.39 | 0.89 | 1.56 |
| -10 / 40 | 3.25 | 1.20 | 2.71 |
| -10 / 50 | 2.47 | 1.29 | 1.91 |
| 0 / 40 | 5.48 | 1.46 | 3.76 |
| 0 / 50 | 4.54 | 1.65 | 2.76 |
| 0 / 60 | 3.55 | 1.81 | 1.97 |
| 10 / 40 | 8.49 | 1.66 | 5.10 |
| 10 / 50 | 7.20 | 1.98 | 3.64 |
| 10 / 60 | 5.89 | 2.17 | 2.72 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland CR24K6M-TFD (R22 hermetic recip, 60 Hz, HT) | R22 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.