Compressor — R22 compressor — 7.1 kW cooling, 2.51 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland CR33K8M-PFZ (R22 hermetic recip, 50 Hz, HT) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 7.11 kW |
| Input power @ 7.2/54.4 °C | 2.51 kW |
| COP @ 7.2/54.4 °C | 2.84 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 5.27 | 1.57 | 3.36 |
| -10 / 40 | 4.03 | 1.70 | 2.36 |
| 0 / 30 | 8.36 | 1.72 | 4.87 |
| 0 / 40 | 6.88 | 1.98 | 3.48 |
| 0 / 60 | 4.77 | 2.30 | 2.08 |
| 10 / 30 | 12.54 | 1.71 | 7.35 |
| 10 / 40 | 10.77 | 2.13 | 5.06 |
| 10 / 60 | 7.90 | 2.77 | 2.85 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |