Catalog · Copeland

Copeland CS33K6E-TF5 (R134A hermetic recip, 50 Hz, HT)

Compressor — R134a compressor — 8.5 kW cooling, 3.19 kW input, COP 2.65 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland CS33K6E-TF5 (R134A hermetic recip, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool23.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C8.46 kW
Input power @ 7.2/54.4 °C3.19 kW
COP @ 7.2/54.4 °C2.65

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 303.221.502.15
-20 / 402.621.521.73
-10 / 305.731.893.03
-10 / 404.681.982.36
0 / 309.652.334.15
0 / 408.142.533.22
0 / 605.322.761.93
10 / 3014.472.575.64
10 / 4012.472.914.28
10 / 608.833.522.51

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland CS33K6E-TF5 (R134A hermetic recip, 60 Hz, HT)R134a
compressorsCopeland CS33K6E-TFD (R404A hermetic recip, 60 Hz, EM)R404A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy