Copeland RRT62C1E-IAV (R134A hermetic recip, 60 Hz, HT)

Compressor — R134a compressor — 1.6 kW cooling, 0.85 kW input, COP 1.88 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RRT62C1E-IAV (R134A hermetic recip, 60 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool23.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.59 kW
Input power @ 7.2/54.4 °C0.85 kW
COP @ 7.2/54.4 °C1.88

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 300.710.401.78
-20 / 400.610.421.47
-10 / 301.160.492.37
-10 / 400.990.531.88
0 / 301.810.593.07
0 / 401.550.652.40
0 / 601.120.781.43
10 / 302.620.693.79
10 / 402.260.772.93
10 / 601.650.951.74

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RRT62C1E-IAB (R450A hermetic recip, 50 Hz, HT)R450A
compressorsCopeland RRT62C1E-IAA (R450A hermetic recip, 60 Hz, HT)R450A
compressorsCopeland RRT62C1E-IAB (R513A hermetic recip, 50 Hz, HT)R513A
compressorsCopeland RRT62C1E-IAA (R513A hermetic recip, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy