Compressor — R513A compressor — 1.4 kW cooling, 0.72 kW input, COP 1.95 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland RRT62C1E-IAB (R513A hermetic recip, 50 Hz, HT) |
| Refrigerant | R513A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 23.6 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 1.40 kW |
| Input power @ 7.2/54.4 °C | 0.72 kW |
| COP @ 7.2/54.4 °C | 1.95 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 13 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 0.62 | 0.36 | 1.71 |
| -20 / 40 | 0.54 | 0.38 | 1.41 |
| -20 / 60 | 0.41 | 0.37 | 1.11 |
| -10 / 30 | 1.04 | 0.44 | 2.36 |
| -10 / 40 | 0.90 | 0.47 | 1.90 |
| -10 / 60 | 0.63 | 0.54 | 1.17 |
| 0 / 30 | 1.58 | 0.52 | 3.05 |
| 0 / 40 | 1.38 | 0.55 | 2.50 |
| 0 / 60 | 0.94 | 0.66 | 1.42 |
| 10 / 30 | 2.31 | 0.67 | 3.42 |
| 10 / 40 | 2.02 | 0.69 | 2.92 |
| 10 / 60 | 1.39 | 0.82 | 1.70 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland RRT62C1E-IAV (R134A hermetic recip, 60 Hz, HT) | R134a |
| compressors | Copeland RRT62C1E-IAB (R450A hermetic recip, 50 Hz, HT) | R450A |
| compressors | Copeland RRT62C1E-IAA (R450A hermetic recip, 60 Hz, HT) | R450A |
| compressors | Copeland RRT62C1E-IAA (R513A hermetic recip, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.