Catalog · Copeland

Copeland RRT64C1E-CAV (R134A hermetic recip, 60 Hz, HT)

Compressor — R134a compressor — 2.0 kW cooling, 0.90 kW input, COP 2.17 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RRT64C1E-CAV (R134A hermetic recip, 60 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool23.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.95 kW
Input power @ 7.2/54.4 °C0.90 kW
COP @ 7.2/54.4 °C2.17

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 300.880.471.87
-20 / 400.740.491.50
-10 / 301.400.562.48
-10 / 401.210.612.00
0 / 302.140.663.25
0 / 401.880.722.62
0 / 601.390.841.66
10 / 303.100.764.09
10 / 402.740.833.30
10 / 602.050.992.07

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RRT64C1E-CAB (R450A hermetic recip, 50 Hz, HT)R450A
compressorsCopeland RRT64C1E-CAA (R450A hermetic recip, 60 Hz, HT)R450A
compressorsCopeland RRT64C1E-CAB (R513A hermetic recip, 50 Hz, HT)R513A
compressorsCopeland RRT64C1E-CAA (R513A hermetic recip, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy