Catalog · Copeland

Copeland RRT64C1E-CAB (R513A hermetic recip, 50 Hz, HT)

Compressor — R513A compressor — 1.7 kW cooling, 0.78 kW input, COP 2.22 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RRT64C1E-CAB (R513A hermetic recip, 50 Hz, HT)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool23.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.72 kW
Input power @ 7.2/54.4 °C0.78 kW
COP @ 7.2/54.4 °C2.22

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 13 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 300.780.391.97
-20 / 400.670.421.60
-20 / 600.460.421.09
-10 / 301.250.472.65
-10 / 401.080.512.12
-10 / 600.750.581.31
0 / 301.920.563.42
0 / 401.660.602.77
0 / 601.170.711.65
10 / 302.780.713.93
10 / 402.410.743.27
10 / 601.710.871.97

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RRT64C1E-CAV (R134A hermetic recip, 60 Hz, HT)R134a
compressorsCopeland RRT64C1E-CAB (R450A hermetic recip, 50 Hz, HT)R450A
compressorsCopeland RRT64C1E-CAA (R450A hermetic recip, 60 Hz, HT)R450A
compressorsCopeland RRT64C1E-CAA (R513A hermetic recip, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy