Compressor — R513A compressor — 1.7 kW cooling, 0.78 kW input, COP 2.22 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland RRT64C1E-CAB (R513A hermetic recip, 50 Hz, HT) |
| Refrigerant | R513A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 23.6 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 1.72 kW |
| Input power @ 7.2/54.4 °C | 0.78 kW |
| COP @ 7.2/54.4 °C | 2.22 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 13 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 0.78 | 0.39 | 1.97 |
| -20 / 40 | 0.67 | 0.42 | 1.60 |
| -20 / 60 | 0.46 | 0.42 | 1.09 |
| -10 / 30 | 1.25 | 0.47 | 2.65 |
| -10 / 40 | 1.08 | 0.51 | 2.12 |
| -10 / 60 | 0.75 | 0.58 | 1.31 |
| 0 / 30 | 1.92 | 0.56 | 3.42 |
| 0 / 40 | 1.66 | 0.60 | 2.77 |
| 0 / 60 | 1.17 | 0.71 | 1.65 |
| 10 / 30 | 2.78 | 0.71 | 3.93 |
| 10 / 40 | 2.41 | 0.74 | 3.27 |
| 10 / 60 | 1.71 | 0.87 | 1.97 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland RRT64C1E-CAV (R134A hermetic recip, 60 Hz, HT) | R134a |
| compressors | Copeland RRT64C1E-CAB (R450A hermetic recip, 50 Hz, HT) | R450A |
| compressors | Copeland RRT64C1E-CAA (R450A hermetic recip, 60 Hz, HT) | R450A |
| compressors | Copeland RRT64C1E-CAA (R513A hermetic recip, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.