Copeland RRT81C1E-PFV (R513A hermetic recip, 60 Hz, HT)

Compressor — R513A compressor — 2.8 kW cooling, 1.09 kW input, COP 2.56 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RRT81C1E-PFV (R513A hermetic recip, 60 Hz, HT)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool23.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C2.78 kW
Input power @ 7.2/54.4 °C1.09 kW
COP @ 7.2/54.4 °C2.56

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 23.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 13 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 301.140.552.08
-20 / 400.910.561.63
-20 / 600.760.661.16
-10 / 301.940.702.77
-10 / 401.600.722.23
-10 / 600.970.741.32
0 / 302.910.763.82
0 / 402.610.882.99
0 / 601.820.991.83
10 / 303.580.517.05
10 / 403.470.814.31
10 / 602.801.202.34

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RRT81C1E-PFV (R134A hermetic recip, 60 Hz, HT)R134a
compressorsCopeland RRT81C1E-PFZ (R450A hermetic recip, 50 Hz, HT)R450A
compressorsCopeland RRT81C1E-PFV (R450A hermetic recip, 60 Hz, HT)R450A
compressorsCopeland RRT81C1E-PFZ (R513A hermetic recip, 50 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy