Copeland RST68C2U-CFA (R290 hermetic recip, 60 Hz, EM)

Compressor — R290 compressor — 2.9 kW cooling, 1.31 kW input, COP 2.18 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland RST68C2U-CFA (R290 hermetic recip, 60 Hz, EM)
RefrigerantR290
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K
Cooling capacity @ 7.2/54.4 °C2.87 kW
Input power @ 7.2/54.4 °C1.31 kW
COP @ 7.2/54.4 °C2.18

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 4-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 301.560.762.05
-20 / 401.350.811.67
-20 / 600.920.871.05
-10 / 302.360.882.67
-10 / 402.060.952.18
-10 / 601.431.071.34

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland RST68C2U-CFA (R454C hermetic recip, 60 Hz, EM)R454C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy