Compressor — R410A compressor — 14.2 kW cooling, 4.87 kW input, COP 2.91 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland XHV0382P-4E9 (R410A variable-speed scroll) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 14.17 kW |
| Input power @ 7.2/54.4 °C | 4.87 kW |
| COP @ 7.2/54.4 °C | 2.91 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 12-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 7.35 | 2.81 | 2.61 |
| -10 / 30 | 11.01 | 2.90 | 3.80 |
| -10 / 40 | 10.00 | 3.50 | 2.85 |
| 0 / 30 | 15.94 | 2.94 | 5.42 |
| 0 / 40 | 14.53 | 3.60 | 4.03 |
| 0 / 60 | 11.42 | 5.31 | 2.15 |
| 10 / 30 | 22.38 | 2.95 | 7.58 |
| 10 / 40 | 20.48 | 3.65 | 5.60 |
| 10 / 60 | 16.34 | 5.49 | 2.98 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.