Compressor — R410A compressor — 9.0 kW cooling, 3.42 kW input, COP 2.62 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland XPV0182E-9E9 (R410A variable-speed scroll, 3 steps) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 8.96 kW |
| Input power @ 7.2/54.4 °C | 3.42 kW |
| COP @ 7.2/54.4 °C | 2.62 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 12-sided polygon. It publishes 3 part-load steps (AHRI 540 §5.3.3), which the solver interpolates between. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 4.86 | 2.10 | 2.31 |
| -10 / 30 | 7.15 | 2.18 | 3.28 |
| -10 / 40 | 6.46 | 2.60 | 2.49 |
| 0 / 30 | 10.26 | 2.19 | 4.69 |
| 0 / 40 | 9.29 | 2.64 | 3.52 |
| 0 / 60 | 7.23 | 3.73 | 1.94 |
| 10 / 30 | 14.28 | 2.12 | 6.74 |
| 10 / 40 | 13.00 | 2.61 | 4.99 |
| 10 / 60 | 10.29 | 3.79 | 2.71 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.