Copeland XPV0382E-4E9 (R410A variable-speed scroll, 3 steps)

Compressor — R410A compressor — 19.5 kW cooling, 6.87 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland XPV0382E-4E9 (R410A variable-speed scroll, 3 steps)
RefrigerantR410A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C19.47 kW
Input power @ 7.2/54.4 °C6.87 kW
COP @ 7.2/54.4 °C2.84

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 12-sided polygon. It publishes 3 part-load steps (AHRI 540 §5.3.3), which the solver interpolates between. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 309.963.932.54
-10 / 3015.044.073.70
-10 / 4013.614.942.76
0 / 3022.114.115.38
0 / 4020.115.073.97
0 / 6015.507.552.05
10 / 3031.153.947.91
10 / 4028.405.055.62
10 / 6022.307.782.87

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy