Catalog · Copeland

Copeland YBD100KAE-TFD (R134A scroll, 50 Hz, HT)

Compressor — R134a compressor — 27.6 kW cooling, 9.72 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YBD100KAE-TFD (R134A scroll, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C27.65 kW
Input power @ 7.2/54.4 °C9.72 kW
COP @ 7.2/54.4 °C2.84

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3017.835.663.15
-10 / 5013.438.621.56
0 / 3027.585.874.70
0 / 5021.818.732.50
0 / 7014.5013.591.07
10 / 3040.496.216.52
10 / 5032.888.963.67
10 / 7023.5013.641.72

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YBD100KAE-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YBD100KAE-TFD (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland YBD100KAE-TFD (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland YBD100KAE-TFD (R513A scroll, 50 Hz, HT)R513A
compressorsCopeland YBD100KAE-TFD (R513A scroll, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy