Catalog · Copeland

Copeland YF13KAE-PFV (R407A scroll, 50 Hz, LL)

Compressor — R407A compressor — 13.7 kW cooling, 5.14 kW input, COP 2.67 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YF13KAE-PFV (R407A scroll, 50 Hz, LL)
RefrigerantR407A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool47.2 / 0.0 K
Cooling capacity @ 7.2/54.4 °C13.70 kW
Input power @ 7.2/54.4 °C5.14 kW
COP @ 7.2/54.4 °C2.67

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 47.2 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 102.891.481.95
-40 / 302.442.041.19
-30 / 104.741.672.83
-30 / 304.032.411.67
-20 / 107.521.874.03
-20 / 306.342.722.33

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YF13KAE-PFV (R134A scroll, 50 Hz, ML)R134a
compressorsCopeland YF13KAE-PFV (R404A scroll, 50 Hz, LL)R404A
compressorsCopeland YF13KAE-PFV (R407F scroll, 50 Hz, LL)R407F
compressorsCopeland YF13KAE-PFV (R448A scroll, 50 Hz, LL)R448A
compressorsCopeland YF13KAE-PFV (R449A scroll, 50 Hz, LL)R449A
compressorsCopeland YF13KAE-TF5 (R454A scroll, 50 Hz, LL)R454A
compressorsCopeland YF13KAE-TF5 (R454A scroll, 60 Hz, LL)R454A
compressorsCopeland YF13KAE-TF5 (R454C scroll, 50 Hz, LL)R454C
compressorsCopeland YF13KAE-TF5 (R454C scroll, 60 Hz, LL)R454C
compressorsCopeland YF13KAE-TF5 (R455A scroll, 50 Hz, LL)R455A
compressorsCopeland YF13KAE-TF5 (R455A scroll, 60 Hz, LL)R455A
compressorsCopeland YF13KAE-PFV (R507 scroll, 50 Hz, LL)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy