Catalog · Copeland

Copeland YH11K1E-TFD (R513A scroll, 60 Hz, HP)

Compressor — R513A compressor — 11.4 kW cooling, 3.71 kW input, COP 3.07 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YH11K1E-TFD (R513A scroll, 60 Hz, HP)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool25.8 / 0.0 K
Cooling capacity @ 7.2/54.4 °C11.38 kW
Input power @ 7.2/54.4 °C3.71 kW
COP @ 7.2/54.4 °C3.07

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 25.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 10 °C, condensing 21 to 65 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 304.911.982.48
-20 / 404.302.421.78
-20 / 603.043.600.85
-10 / 307.732.123.65
-10 / 406.852.562.67
-10 / 605.003.741.34
0 / 3011.752.305.11
0 / 4010.462.743.81
0 / 607.733.931.97
10 / 3017.302.516.90
10 / 4015.462.965.23
10 / 6011.594.152.79

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YH11K1E-PFJ (R1234yf scroll, 50 Hz, HP)R1234yf
compressorsCopeland YH11K1E-TFD (R1234yf scroll, 60 Hz, HP)R1234yf
compressorsCopeland YH11K1E-TFD (R134A scroll, 60 Hz, HP)R134a
compressorsCopeland YH11K1E-TFD (R407C scroll, 60 Hz, HP)R407C
compressorsCopeland YH11K1E-TFD (R454C scroll, 60 Hz, HP)R454C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy