Catalog · Copeland

Copeland YS09KAE-PFJ (R404A scroll, 50 Hz, EM)

Compressor — R404A compressor — 3.1 kW cooling, 1.38 kW input, COP 2.21 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS09KAE-PFJ (R404A scroll, 50 Hz, EM)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C3.06 kW
Input power @ 7.2/54.4 °C1.38 kW
COP @ 7.2/54.4 °C2.21

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 101.500.512.96
-30 / 301.180.691.70
-20 / 102.240.564.01
-20 / 301.810.792.28
-20 / 601.101.410.78
-10 / 103.340.546.21
-10 / 302.690.863.14
-10 / 601.601.461.09
0 / 303.900.874.47
0 / 602.281.521.50

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS09KAE-PFJ (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland YS09KAE-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YS09KAE-PFJ (R22 scroll, 50 Hz, HT)R22
compressorsCopeland YS09KAE-PFJ (R22 scroll, 60 Hz, HT)R22
compressorsCopeland YS09KAE-PFJ (R407A scroll, 50 Hz, EM)R407A
compressorsCopeland YS09KAE-TF5 (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland YS09KAE-TF5 (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland YS09KAE-PFJ (R448A scroll, 50 Hz, EM)R448A
compressorsCopeland YS09KAE-PFJ (R449A scroll, 50 Hz, EM)R449A
compressorsCopeland YS09KAE-PFJ (R507 scroll, 50 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy