Catalog · Copeland

Copeland YS12KAE-TF5 (R134A scroll, 50 Hz, HT)

Compressor — R134a compressor — 3.1 kW cooling, 1.08 kW input, COP 2.86 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS12KAE-TF5 (R134A scroll, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool18.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C3.08 kW
Input power @ 7.2/54.4 °C1.08 kW
COP @ 7.2/54.4 °C2.86

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 302.030.653.10
-10 / 501.640.941.75
0 / 303.090.654.72
0 / 502.480.982.54
0 / 701.851.381.34
10 / 304.550.617.41
10 / 503.691.013.67
10 / 702.741.431.91

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS12KAE-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland YS12KAE-PFJ (R22 scroll, 50 Hz, HT)R22
compressorsCopeland YS12KAE-PFJ (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland YS12KAE-PFJ (R407A scroll, 50 Hz, MT)R407A
compressorsCopeland YS12KAE-TF5 (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland YS12KAE-TF5 (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland YS12KAE-PFJ (R448A scroll, 50 Hz, EM)R448A
compressorsCopeland YS12KAE-PFJ (R449A scroll, 50 Hz, EM)R449A
compressorsCopeland YS12KAE-PFJ (R507 scroll, 50 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy