Catalog · Copeland

Copeland YS13KSE-PFV (R134A scroll, 50 Hz, EM)

Compressor — R134a compressor — 3.5 kW cooling, 1.35 kW input, COP 2.61 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland YS13KSE-PFV (R134A scroll, 50 Hz, EM)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C3.52 kW
Input power @ 7.2/54.4 °C1.35 kW
COP @ 7.2/54.4 °C2.61

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 300.950.651.46
-30 / 400.870.761.14
-20 / 301.520.771.99
-20 / 401.390.911.53
-10 / 302.390.822.93
-10 / 402.170.992.18
-10 / 601.711.381.23
0 / 303.630.824.42
0 / 403.281.023.21
0 / 602.561.471.74

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland YS13KSE-PFV (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland YS13KSE-TF5 (R454A scroll, 50 Hz, EM)R454A
compressorsCopeland YS13KSE-TF5 (R454A scroll, 60 Hz, EM)R454A
compressorsCopeland YS13KSE-TF5 (R454C scroll, 50 Hz, EM)R454C
compressorsCopeland YS13KSE-TF5 (R454C scroll, 60 Hz, EM)R454C
compressorsCopeland YS13KSE-TF5 (R455A scroll, 50 Hz, EM)R455A
compressorsCopeland YS13KSE-TF5 (R455A scroll, 60 Hz, EM)R455A
compressorsCopeland YS13KSE-PFV (R507 scroll, 50 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy