Compressor — R134a compressor — 4.4 kW cooling, 1.63 kW input, COP 2.71 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YS17KSE-PFV (R134A scroll, 50 Hz, EM) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.6 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 4.40 kW |
| Input power @ 7.2/54.4 °C | 1.63 kW |
| COP @ 7.2/54.4 °C | 2.71 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 30 | 1.17 | 0.79 | 1.49 |
| -30 / 40 | 1.07 | 0.92 | 1.16 |
| -20 / 30 | 1.89 | 0.92 | 2.06 |
| -20 / 40 | 1.72 | 1.09 | 1.58 |
| -10 / 30 | 2.98 | 0.98 | 3.03 |
| -10 / 40 | 2.70 | 1.19 | 2.27 |
| -10 / 60 | 2.11 | 1.66 | 1.27 |
| 0 / 30 | 4.53 | 1.00 | 4.54 |
| 0 / 40 | 4.10 | 1.23 | 3.33 |
| 0 / 60 | 3.19 | 1.76 | 1.81 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YS17KSE-PFV (R404A scroll, 50 Hz, EM) | R404A |
| compressors | Copeland YS17KSE-TF5 (R454A scroll, 50 Hz, EM) | R454A |
| compressors | Copeland YS17KSE-TF5 (R454A scroll, 60 Hz, EM) | R454A |
| compressors | Copeland YS17KSE-TF5 (R454C scroll, 50 Hz, EM) | R454C |
| compressors | Copeland YS17KSE-TF5 (R454C scroll, 60 Hz, EM) | R454C |
| compressors | Copeland YS17KSE-TF5 (R455A scroll, 50 Hz, EM) | R455A |
| compressors | Copeland YS17KSE-TF5 (R455A scroll, 60 Hz, EM) | R455A |
| compressors | Copeland YS17KSE-PFV (R507 scroll, 50 Hz, EM) | R507 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.