Compressor — R507 compressor with a 10-coefficient AHRI 540 map.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YS18KSE-PFV (R507 scroll, 50 Hz, EM) |
| Refrigerant | R507 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.6 / 0.0 K |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 3.38 | 1.11 | 3.04 |
| -30 / 30 | 2.78 | 1.55 | 1.79 |
| -20 / 10 | 5.15 | 1.20 | 4.30 |
| -20 / 30 | 4.20 | 1.75 | 2.40 |
| -20 / 60 | 2.49 | 2.77 | 0.90 |
| -10 / 10 | 7.64 | 1.25 | 6.10 |
| -10 / 30 | 6.14 | 1.89 | 3.25 |
| -10 / 60 | 3.60 | 3.10 | 1.16 |
| 0 / 30 | 8.76 | 1.96 | 4.47 |
| 0 / 60 | 5.10 | 3.33 | 1.53 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YS18KSE-PFV (R404A scroll, 50 Hz, EM) | R404A |
| compressors | Copeland YS18KSE-TF5 (R454A scroll, 50 Hz, EM) | R454A |
| compressors | Copeland YS18KSE-TF5 (R454A scroll, 60 Hz, EM) | R454A |
| compressors | Copeland YS18KSE-TF5 (R454C scroll, 50 Hz, EM) | R454C |
| compressors | Copeland YS18KSE-TF5 (R454C scroll, 60 Hz, EM) | R454C |
| compressors | Copeland YS18KSE-TF5 (R455A scroll, 50 Hz, EM) | R455A |
| compressors | Copeland YS18KSE-TF5 (R455A scroll, 60 Hz, EM) | R455A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.