Compressor — R290 compressor — 7.6 kW cooling, 2.69 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland YS23KAU-TF5 (R290 scroll, 50 Hz, MT) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.6 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 7.63 kW |
| Input power @ 7.2/54.4 °C | 2.69 kW |
| COP @ 7.2/54.4 °C | 2.84 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 3.25 | 0.97 | 3.35 |
| -30 / 30 | 2.72 | 1.39 | 1.96 |
| -20 / 10 | 4.82 | 1.08 | 4.45 |
| -20 / 30 | 4.08 | 1.55 | 2.63 |
| -20 / 60 | 2.85 | 2.52 | 1.13 |
| -10 / 10 | 6.97 | 1.17 | 5.97 |
| -10 / 30 | 5.92 | 1.66 | 3.57 |
| -10 / 60 | 4.11 | 2.77 | 1.49 |
| 0 / 30 | 8.35 | 1.71 | 4.87 |
| 0 / 60 | 5.81 | 2.92 | 1.99 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland YS23KAU-TF5 (R290 scroll, 60 Hz, MT) | R290 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.