Compressor — R22 compressor — 41.7 kW cooling, 13.39 kW input, COP 3.12 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZB114KC-TED (R22 scroll, 50 Hz, HT) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 41.75 kW |
| Input power @ 7.2/54.4 °C | 13.39 kW |
| COP @ 7.2/54.4 °C | 3.12 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 29.05 | 7.79 | 3.73 |
| -10 / 40 | 25.50 | 9.63 | 2.65 |
| 0 / 30 | 42.49 | 8.09 | 5.25 |
| 0 / 40 | 38.52 | 9.83 | 3.92 |
| 10 / 30 | 59.32 | 8.63 | 6.87 |
| 10 / 40 | 54.49 | 10.22 | 5.33 |
| 10 / 60 | 42.48 | 15.10 | 2.81 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZB114KC-TED (R22 scroll, 60 Hz, HT) | R22 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.