Catalog · Copeland

Copeland ZB114KCE-TED (R22 scroll, 60 Hz, HT)

Compressor — R22 compressor — 50.5 kW cooling, 16.56 kW input, COP 3.05 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB114KCE-TED (R22 scroll, 60 Hz, HT)
RefrigerantR22
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C50.45 kW
Input power @ 7.2/54.4 °C16.56 kW
COP @ 7.2/54.4 °C3.05

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3034.839.763.57
-10 / 4031.4111.932.63
0 / 3051.0910.274.97
0 / 4046.2012.293.76
10 / 3073.7511.256.56
10 / 4065.5912.995.05
10 / 6051.5118.582.77

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB114KCE-TFD (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZB114KCE-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZB114KCE-TED (R22 scroll, 50 Hz, HT)R22
compressorsCopeland ZB114KCE-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB114KCE-TFD (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB114KCE-TFD (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland ZB114KCE-TFD (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland ZB114KCE-TFD (R507 scroll, 50 Hz, MT)R507
compressorsCopeland ZB114KCE-TFD (R507 scroll, 60 Hz, MT)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy