Catalog · Copeland

Copeland ZB95KCE-TFD (R134A scroll, 50 Hz, HT)

Compressor — R134a compressor — 23.2 kW cooling, 7.98 kW input, COP 2.90 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB95KCE-TFD (R134A scroll, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C23.16 kW
Input power @ 7.2/54.4 °C7.98 kW
COP @ 7.2/54.4 °C2.90

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3014.944.703.18
-10 / 5011.776.671.76
0 / 3023.004.894.70
0 / 5018.367.142.57
0 / 7013.349.991.33
10 / 3033.814.677.24
10 / 5027.417.473.67
10 / 7020.2210.501.93

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB95KCE-TED (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZB95KCE-TED (R22 scroll, 50 Hz, HT)R22
compressorsCopeland ZB95KCE-TED (R22 scroll, 60 Hz, HT)R22
compressorsCopeland ZB95KCE-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB95KCE-TED (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB95KCE-TFD (R507 scroll, 50 Hz, MT)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy