Catalog · Copeland

Copeland ZBD114K5E-TFD (R513A scroll, 60 Hz, HT)

Compressor — R513A compressor — 33.3 kW cooling, 12.22 kW input, COP 2.73 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZBD114K5E-TFD (R513A scroll, 60 Hz, HT)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool18.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C33.32 kW
Input power @ 7.2/54.4 °C12.22 kW
COP @ 7.2/54.4 °C2.73

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3023.437.213.25
-10 / 5017.9910.571.70
0 / 3034.977.604.60
0 / 5027.2910.972.49
0 / 7018.7016.131.16
10 / 3049.547.866.31
10 / 5039.2911.423.44
10 / 7027.1016.301.66

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZBD114K5E-TFD (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZBD114K5E-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZBD114K5E-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZBD114K5E-TFD (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZBD114K5E-TFD (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland ZBD114K5E-TFD (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland ZBD114K5E-TFD (R448A scroll, 60 Hz, MT)R448A
compressorsCopeland ZBD114K5E-TFD (R449A scroll, 60 Hz, MT)R449A
compressorsCopeland ZBD114K5E-TFD (R513A scroll, 50 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy