Catalog · Copeland

Copeland ZF13K4E-TF5 (R507 scroll, 50 Hz, LL)

Compressor — R507 compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZF13K4E-TF5 (R507 scroll, 50 Hz, LL)
RefrigerantR507
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool34.7 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 34.7 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 7-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / -03.541.192.97
-40 / 302.601.931.34
-30 / -05.451.284.26
-30 / 304.102.201.86
-20 / 306.182.472.50
0 / 3012.822.884.45
0 / 607.484.711.59

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZF13K4E-TF5 (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZF13K4E-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZF13K4E-TF5 (R404A scroll, 50 Hz, LL)R404A
compressorsCopeland ZF13K4E-TF5 (R404A scroll, 60 Hz, LL)R404A
compressorsCopeland ZF13K4E-TF5 (R407A scroll, 50 Hz, LL)R407A
compressorsCopeland ZF13K4E-TF5 (R407A scroll, 60 Hz, LL)R407A
compressorsCopeland ZF13K4E-TF5 (R407C scroll, 60 Hz, LL)R407C
compressorsCopeland ZF13K4E-TF5 (R407F scroll, 50 Hz, LL)R407F
compressorsCopeland ZF13K4E-TF5 (R407F scroll, 60 Hz, LL)R407F
compressorsCopeland ZF13K4E-TF5 (R448A scroll, 50 Hz, LL)R448A
compressorsCopeland ZF13K4E-TF5 (R448A scroll, 60 Hz, LL)R448A
compressorsCopeland ZF13K4E-TF5 (R449A scroll, 50 Hz, LL)R449A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy