Compressor — R290 compressor — 7.7 kW cooling, 2.51 kW input, COP 3.08 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZH06KCU-TFD (R290 scroll, 60 Hz, HP) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 2.8 K |
| Cooling capacity @ 7.2/54.4 °C | 7.74 kW |
| Input power @ 7.2/54.4 °C | 2.51 kW |
| COP @ 7.2/54.4 °C | 3.08 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 5.68 | 1.58 | 3.61 |
| -10 / 40 | 5.11 | 1.85 | 2.77 |
| 0 / 30 | 8.22 | 1.66 | 4.95 |
| 0 / 40 | 7.43 | 1.94 | 3.84 |
| 0 / 60 | 5.72 | 2.67 | 2.15 |
| 10 / 30 | 11.48 | 1.78 | 6.43 |
| 10 / 40 | 10.43 | 2.04 | 5.11 |
| 10 / 60 | 8.16 | 2.78 | 2.94 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZH06KCU-PFV (R290 scroll, 50 Hz, HP) | R290 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.