Catalog · Copeland

Copeland ZH09KCU-PFV (R290 scroll, 50 Hz, HP)

Compressor — R290 compressor — 9.2 kW cooling, 3.23 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZH09KCU-PFV (R290 scroll, 50 Hz, HP)
RefrigerantR290
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 2.8 K
Cooling capacity @ 7.2/54.4 °C9.18 kW
Input power @ 7.2/54.4 °C3.23 kW
COP @ 7.2/54.4 °C2.84

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 203.191.731.85
-30 / 402.512.221.13
-20 / 204.961.832.71
-20 / 403.992.391.67
-10 / 207.451.903.93
-10 / 406.062.492.44
-10 / 703.773.701.02
10 / 4012.462.634.75
10 / 708.134.121.97

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZH09KCU-TFD (R290 scroll, 60 Hz, HP)R290

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy